• Onboard Home
  • Youtube Channel
  • Ask Community
Ask Community
Frequently Asked Questions
General
General
Overview
Getting Started
Installation
Installation
Steps To Success
Creating Building & Deployment
Installing Edge Node
Installing Edge Node on Hyper-V
Troubleshooting Installation & Working with IT
Data Collection
Data Collection
What is BACnet?
BACnet Discovery
What is Modbus?
Connect Your Modbus Devices
Troubleshooting Discovery
Understanding Real-Time Data Collection
Dealing with Offline Data
Multi-Subnet BACnet Network
Data Modeling with AI
Data Modeling with AI
What is an Ontology?
Onboard's Data Model
Getting Started with Staging
Onboard AI
Equipment Tab
Points Tab
Locations Tab
Publish-Unpublish Workflow
Feature Guides
Feature Guides
Exporting Data (CSV, JSON)
Buildings Explorer
Creating Custom Labels
Account & Preferences
Account & Preferences
User Roles & Access
Creating a User Account
Deactivating a User Account
Unit Preferences
Security
Security
Security Brief

Connect Your Modbus Devices

The Modbus Tab on the Deployments page lets you add, configure, and manage Modbus IP devices within your building deployment.

Onboard supports a pre-defined set of vendor templates for Modbus. To confirm if your Modbus device is supported, please review the Network & Connectivity Requirements article and verify the Connectivity Requirements section before proceeding.

Adding a New Modbus Device

  1. On the Modbus tab, Click “ADD NEW MODBUS” button
  2. This opens the launch interface where you will enter details about your device.‍
  3. Enter Device Information‍
    • Controller IP: The IP address of your Modbus device. Ensure it is accessible to the Edge Node on your network. ‍
    • Port Number: By default, Modbus uses port# 502.‍
    • Unit Identifier: This identifies the Modbus device on the network (often called slave ID). You can find it in your device documentation or front-end configuration.‍
    • Vendor Device: Choose from Onboard’s supported vendor templates. These templates map registers to equipment and point types automatically.‍
    • Polling Frequency: Define how often the Edge Node should query the Modbus device (default: 60 seconds).‍
  4. Save Configuration
  5. Once you save, the Edge Node attempts to connect to the Modbus device. The device will now appear under the Modbus tab with an indicated status.

Understanding Device Status

NEW ...device configuration has been added and the Edge Node is attempting connection. Allow 15–20 minutes.
SUCCESS ...connection was successful. Visit Staging to confirm points from this device appear, then publish to begin trending data.
FAILED ...connection was unsuccessful. Check the IP, port, and unit ID, then try again. See Troubleshooting Discovery for next steps.

🔄 To retry the same configuration, use the refresh button under the Actions column.

🗑️ To correct configuration details, delete the device and re-add it with the proper settings (the UI does not currently support editing existing configurations).

‍

⚠️ One Active Collector Only: To connect with a Modbus device, make sure only one Collector is active. You can disable the inactive Collectors via the Management tab or email us if you need assistance.

‍

👉 Next Steps: Once your Modbus device shows SUCCESS, head to Staging to validate and publish its equipment and points.