Troubleshooting Guide
Modbus Connections
Sometimes a Modbus device may fail to connect or return a FAILED status. Here are common issues and how to fix them:
Controller IP Issues
- Problem: The Modbus controller’s IP is incorrect or not accessible.
- Fix: Double-check the device IP in your BAS or device front-end.
Port Configuration
- Problem: Port is closed or incorrect.
- Fix: Default Modbus TCP port is 502. Confirm this port is open and accessible.
Unit Identifier (Slave ID)
- Problem: Wrong unit ID entered.
- Fix:
- Verify the unit identifier in the device’s configuration or vendor manual.
- If multiple devices share the same controller IP, each must have a unique unit ID.
Unsupported Vendor Device
- Problem: Device not listed in Onboard’s Modbus templates.
- Fix:
- Check the Connectivity Requirements documentation for supported models.
- If unsupported, request a template in the Online Community with vendor name and model.